SDS

2of 2
24.5 44
Can 1 Can 2 Can 2 Can 4 Can 5 Can 6 Can 7 Can 8 Can 9
Test
Can 1 Can 2 Can 2 Can 4 Can 5 Can 6 Can 7 Can 8 Can 9
Ignition (Y/N) No No No No No No No No No
Ignition (Y/N)
Ignition (Y/N)
Ignition (Y/N)
Ignition (Y/N)
Ignition (Y/N)
24.5
1 2 3
12 11 14
No No No
Conclusion:
Tested by: Approved by:
Cert # 4305.01
60 cm
Ignition (Y/N)
75 cm
Ignition (Y/N)
105 cm
Ignition (Y/N)
90 cm
Ignition (Y/N)
100 Collip Circle, Suite 220, London, ON N6G 4X8 - www.delltech.com - Tel: 519.858.5021 Fax: 519.858.5026 Ver. 30-10-2015
Level of Filling (%)
Ignition (Y/N)
Ignition (Y/N)
Ignition (Y/N)
Temperature (˚C)
Relative Humidity (%)
Net Volume
13.10
Under the conditions of this test the sample Sabre Red - pepper spray #IT-SPKCR-14-RM
Under the conditions of this test no ignition was observed and the sample Sabre Red - pepper spray #IT-SPKCR-14-RM
should be tested with the Enclosed Space Ignition Test.
This report shall not be reproduced except in full, without the written approval of the laboratory. The results relate only to the items tested.
Test
10 - 12% nominal fill level requires testing of only one (1) can at "the flame
ignition distance of full can + 15 cm and only in one position. Ref. UN Manual of
Test & Criteria Part 3, Section 31.4.3.2(s)
upright
Shaken before discharge?
Yes
Straw/ No Straw?
No Straw
Test position
Dispenser Distance
15 cm
30 cm
45 cm
Inverted position ignition test are performed starting at the distance for which no ignition was observed in upright position. Ref. UN
Manual of Test and Criteria Part 3, Section 31.4.3.2(l)
Test performed at 10 - 12% nominal fill
Can number
Shaken before discharge?
Yes
Yes
Yes
Straw/ No Straw?
No Straw
No Straw
No Straw
Initial level of filling
100%
100%
100%
Test Position?
inverted
inverted
inverted
13.10
Temperature (˚C)
Relative Humidity (%)
Test performed in inverted position
Net
Volume