Specifications

Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 36 © Saftronics, Inc.
6.1 Constant Set-up and Initialization
6.1.1. Constant Selection/Initialization (n001)
The following table describes the data which can be set or read when n001 is selected.
Setting Constant that can be set Constant that can be read
0
(Constant write disable)
n001 n001 to n108
1
(Factory setting)
n001 to n034 n001 to n108
2 n001 to n049 n001 to n108
3 n001 to n108 n001 to n108
4, 5 Not used (disabled)
8 Initialize: 2-wire sequence
9 Initialize: 3-wire sequence
[
[ Refer to Page 50.
6.2 V/f Pattern Setting
V/f pattern can be set by constant n010.
Set value 0 to E: Preset V/f pattern can be selected.
F : Custom V/f pattern can be set.