Specifications

Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 37 © Saftronics, Inc.
6.2.1. Preset V/f Pattern
The following shows the preset V/f patterns. (The voltages are for 200V class. For 400V class, the value is twice that of
200V class.)
Table 13 Preset V/f Pattern (n010 = 0 to E)
Specifications n010 V/f Pattern *1 Specifications n010 V/f Patterns *1
Low
Starting
Torque
8
50 Hz 0 50 Hz
High
Starting
Torque
9
60 Hz
Saturation
1
F
Low
Starting
Torque
A
60 Hz
50 Hz
Saturation
2
High Starting Torque *2
60 Hz
High
Starting
Torque
B
General-Purpose
72 Hz 3 90 Hz C
Variable
Torque 1
4
50 Hz
Variable
Torque 2
5
120 Hz D
Variable
Torque 3
6
Variable Torque Characteristics
60 Hz
Variable
Torque 4
7
High Speed Operation
180 Hz E
1 Consider the following items as the conditions for selecting a V/f pattern. They must be suitable for:
The voltage and frequency characteristics of motor.
The maximum rotation speed of motor.
2 Select high starting torque only in the following conditions. Normally, this selection is not required.
The wiring distance is long (150 meters (492 feet) and above).
Voltage drop at startup is large.
AC Reactor is inserted in the input or output of the Inverter.
A motor smaller than the nominal output of the Inverter is used.
3 Voltages when the models of 200V, 55kW or above, or 400V, 55kW or above are selected.