Specifications

Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 38 © Saftronics, Inc.
6.2.2. Custom V/f Pattern
Set each pattern when using a special motor (high-speed motor, etc.) or when requiring special torque adjustment of
machine.
Make sure to satisfy the following
conditions for setting of constants
n012 to n018.
n017 < n015 < n014 < n012
Figure 18 Custom V/f Pattern Setting
Constant No. Name Unit Setting Range Factory Setting
n012 Maximum output frequency 0.1 Hz
50.0 400.0 Hz
60.0 Hz
n013 Maximum voltage 0.1 V
0.1 255.0 V
[
200.0 V
[
n014
Maximum voltage output
frequency (base frequency)
0.1 Hz 0.2 400.0 Hz 60.0 Hz
n015 Middle output frequency 0.1 Hz
0.1 399.9 Hz
3.0 Hz
n016
Middle output frequency
voltage
0.1 V 0.1 255.0 V
[
15.0 V
[
n017 Minimum output frequency 0.1 Hz
0.1 10.0 Hz
1.5 Hz
n018
Minimum output frequency
voltage
0.1 V 0.1 50.0 V
[
10.0 V
[
For 400 V class, the value is twice that of 200 V class.
Increasing the voltage of the V/f pattern increases motor torque, but an excessive increase may cause the following:
Inverter malfunction because of motor overexcitation.
Motor overheat or excessive vibration.
Increase voltage gradually while verifying the motor current.
6.3 Setting Operation Conditions
6.3.1. Reverse Run Prohibit (n006)
“Reverse run disabled” setting does not accept a reverse RUN command from the control circuit terminal or Digital
Operator. This setting is used for applications where a reverse RUN command can cause problems.
Setting Description
0 Reverse run enabled
1 Reverse run disabled
6.3.2. Multi-Step Selection
By combining frequency reference and input terminal function selections, up to four steps of speed can be set.
Four step speed change
n002 = 1 (Operation mode selection)
n025 = 30.0 Hz
n026 = 40.0 Hz
n027 = 50.0 Hz
n028 = 60.0 Hz
n038 = 9 (Multi-function contact input Terminal S5)
n039 = 10 (Multi-function contact input Terminal S6)