6.3.16 Reducing Motor Noise or Leakage Current (n050)
Sets Inverter output transistor switching frequency (carrier frequency).
Setting Carrier Frequency (kHz)
Metallic Noise from
Motor
Noise and Current
Leakage
1 2.5 Higher Smaller
2 5.0
3 8.0
4 10.0
5 12.5
6 15.0 Not audible Larger
Figure 35 Custom Setting of Carrier Frequency Patterns