Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 50 © Saftronics, Inc.
Figure 40 DC Injection Braking
When coast to stop is specified in stopping method selection (n004), DC Injection Braking at stop does not operate.
6.5 Building Interface Circuits with External Devices
6.5.1. Using Sequence Input Signals (n035 to n039)
Multi-function contact input Terminal S2 to S6 functions can be changed when necessary by setting constants n035 to
n039, respectively. Neither of these parameters can receive a setting common with the other.
Terminal S2 function: Set to n035
Terminal S3 function: Set to n036
Terminal S4 function: Set to n037
Terminal S5 function: Set to n038
Terminal S6 function: Set to n039
Table 14 Multi-Function Input Variables
Setting Name Description Page
0 REV RUN command (2-wire sequence) Only constant n035 can be set. 51
1
FWD/REV RUN command
(3-wire sequence)
Only constant n035 can be set. 51
2 External fault (NO constant input)
3 External fault (NC contact input)
Inverter stops at fault when external fault signal is input.
Digital Operator displays EFo.
4 Fault reset Resets fault. Fault reset is disabled during RUN command input.
5 LOCAL/REMOTE selection
51
6
Serial communication/control circuit
terminal selection
52
7 Fast stop Decelerates to stop by decel time 2 (n022) when fast stop is input.
8
Master frequency reference input level
selection
Master frequency reference input level (voltage input at open, current
input at closed) can be selected.
9 Multi-step speed reference 1
10 Multi-step speed reference 2
38
11 Jog frequency selection
39
12 Accel/decel time selection
41
13 External baseblock (NO contact input)
14 External baseblock (NC contact input)
Coasting signal. Motor starts coasting when the signal is input. Digital
Operator displays bb (blinking).
15
Search command from maximum
frequency
16 Search command from set frequency
Speed Search command signals. 45
17 Constant setting enable/disable
Permission or prohibition of constant setting from the Digital Operator or
serial communication (setting disabled at closed, enabled at open) can be
selected.
18 PID integral value reset
19 PID Control disable
58
20 Timer function
52
21 OH3 (Inverter overheat alarm)
When this signal is input, the Digital Operator displays OH3 (blinking).
Inverter continues operation.
22 Analog reference sample/hold Analog frequency reference is sampled at closed and held at open. 52
25 UP/DOWN command Only constant n039 can be set. 53
26 Loop test Only constant n039 can be set. 53
2 to 6 are displayed in o corresponding to Terminals S2 to S6.
Factory settings: n035=0, n036=2, n037=4, n038=9, n039=10