Specifications

Chapter 6: Programming Features
Firmware – S2011 and S3012
Revision: 1 (9/98) 55 © Saftronics, Inc.
6.5.3. Using Output Signals (n040, n041)
Multi-function contact output Terminals MA, MB and M1 functions can be changed when necessary by setting constants
n040 and n041.
Terminal MA and MB functions: Set to n040.
Terminal M1 function: Set to n041.
Table 16 Multi-Function Output Variables
Setting Name Description Page
0 Fault Closed when Inverter fault occurs.
1 During running
Closed when either FWD or REV RUN command is input or when the Inverter outputs
voltage.
2 Frequency agree
56
3
Desired frequency
agree
56
4 Frequency detection 1
44
5 Frequency detection 2
44
6
Overtorque detection
(NO contact)
43
7
Overtorque detection
(NC contact)
43
8 During baseblock Closed when Inverter output shuts OFF.
9 Operation mode Closed when RUN command or frequency reference from Digital Operator is selected.
10
Inverter operation
ready
Closed when no Inverter fault does not occur and the Inverter can be operated.
11 Timer function
52
12 Automatic restart Closed during fault retry operation.
13 OL pre-alarm
Outputs an alarm before Inverter and motor overload protection are enabled. Pre-alarm level
is 150% for 48 seconds for the Inverter and more than 80% of the overload protection time for
the motor.
14
Frequency reference
loss
Outputs a contact when detecting a rapid decrease in the frequency reference. A rapid
decrease in the frequency reference means that the reference value is reduced more than
90% within 400ms when the reference is input to control circuit terminal.
15
Output from serial
communication
Activates contact output independently from Inverter operation by a command from serial
communications (MEMOBUS).
16 PID feedback loss
Detects a rapid decrease in feedback and outputs a contact when the PID Control mode is
set. Detects when the feedback value decreases less than the detection level (n093) for
longer than the feedback loss detection delay time (n094); the Inverter continues operation.
17 OH1 alarm Closed during heatsink overtemperature (Digital Operator displays OH1” blinking).
Factory settings: n040=0, n041=1