Specifications

Chapter 12: Constant List
Firmware – S2011 and S3012
Revision: 1 (9/98) 89 © Saftronics, Inc.
Table 27 Constant List (Continued)
Constant Function Name Description
Factory
Setting
n109
Slip compensation gain
Unit: : 0.1%
Setting range : 0.0 to 9.9%
0.0%
n110
Motor no-load current
Unit: : 1%
Setting range : 0 to 99%
30%
n111
Primary delay time constant
Unit : 0.1 seconds
Setting range : 0.0 to 25.5 seconds
2.0 seconds
n112
Digital Operator connection fault
detection
0 : Connection fault detection is disabled
1 : Connection fault detection is enabled
0
n113
Frequency agree detection width
selection
Unit : 0.1Hz
Setting range : 0.0 to 25.5Hz
2.0Hz
n114
Function selection at LOCAL/REMOTE
switching
0 : At LOCAL/REMOTE switching, restart is enabled after stop
command is input.
1 : At LOCAL/REMOTE switching, restart is enabled at once.
0
n115
kVA selection
Unit : 1
Setting range :
GP5 (VSP2010): 0 to 8, 20 to 29
FP5 (VSP3010): 9 to F, 2A to 35
n116 CT/VT Selection
0 : Constant Torque
1 : VariableTorque
n117 Low Frequency OL Starting Point
Unit : 0.1Hz
Setting range : 0.0 to 10.0Hz
6.0Hz
n118 0Hz Continuous Operation level
Unit : 1%
Setting range : 25 to 100%
50%
These constants are disabled for former softwares VSP1010 to VSP1015.
Enabled for the following software number (or after).
GP5 : VSP2010
FP5 : VSP3010