User`s manual

FP5/GP5 User’s Manual 25
Chapter 1 - Receiving & Installation
Wiring
Wire and Terminal Screw Sizes
230V Class Wire Size
* Wire sizes are based on 75°C copper wire.
Note:
Voltage drop should be considered when determining wire size. Voltage drop can be
calculated using the following equation:
Select a wire size so that voltage drop will be less than 2% of the normal rated voltage.
Circuit
Model
CIMR-
Terminal Symbol
Terminal
Screw
Wire Size *
Max. Torque
lb-in (N·m)
Wire Type
AWG mm
2
Main
P5U20P4
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M4 14 - 10 2 - 5.5 12.4 (1.4)
Power cable:
600V vinyl
sheathed wire
or equivalent
P5U20P7
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M4 14 - 10 2 - 5.5 12.4 (1.4)
P5U21P5
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M4
14 - 10 2 - 5.5
12.4 (1.4)
12 - 103.5 - 5.5
P5U22P2
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M4 12 - 103.5 - 5.5 12.4 (1.4)
P5U23P7
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M4 10 5.5 12.4 (1.4)
P5U25P5
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M5
8 8
22.1 (2.5)
10 - 8 5.5 - 8
P5U27P5
L1, L2, L3, , 1, 2, B1, B2, T1, T2, T3
M5
8 8
22.1 (2.5)
10 - 8 5.5 - 8
P5U2011
L1, L2, L3, , 1, 2, 3, T1, T2, T3
M6
4 22
45.1 (5.1)
8 8
P5U2015
L1, L2, L3, , 1, 2, 3, T1, T2, T3 M8 3 30 90.3 (10.2)
M6 8 8 45.1 (5.1)
P5U2018
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8
3 30
90.3 (10.2)
6 14
P5U2022
L1, L2, L3, L11, L21, L31, T1, T2, T3
M8
2 38
90.3 (10.2)
6 14
P5U2030
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 4/0 100 203.6 (23.0)
M8 4 22 90.3 (10.2)
P5U2037
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P60 x 2P 203.6 (23.0)
M8 4 22 90.3 (10.2)
P5U2045
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P60 x 2P 203.6 (23.0)
M8 4 22 90.3 (10.2)
P5U2055
L1, L2, L3, L11, L21, L31, T1, T2, T3 M10 1/0 x 2P60 x 2P 203.6 (23.0)
M8 3 30 90.3 (10.2)
P5U2075
L1, L2, L3, L11, L21, L31, T1, T2, T3 M12 4/0 x 2P100 x 2P349.6 (39.5)
M8 1 50 90.3 (10.2)
Control
Common
to all
models
S1, S2, S3, S4, S5, S6, SC
FV, FI, FS, FC
AM, AC, M1, M2, MA, MB, MC
- 20 - 16
Stranded
0.5 - 1.25
Solid
0.5 - 1.25
-
Twisted
shielded wire
with Class 1
wiring
G M3.5 20 - 14 0.5 - 2 8.9 (1.0)
Phase-to phase voltage drop (V)
wire resistance (/km) x wiring distance (m) x current (A) x 10
-3
3=
efesotomasyon.com - Control Techniques,emerson,saftronics -ac drive-servo motor