2.4 OPERATION MODE SELECTION (n002, Oper Mode Select)
The FP5/GP5 has two operation modes: LOCAL and REMOTE
(see table below for description). These two modes can be selected by the
digital operator “LOCAL/REMOTE” key only when operation is stopped.
The operation mode selected can be verified by observing the SEQ and
REF LEDs on the digital operator (as shown below). The operation mode
is set to REMOTE (run by control circuit terminals FV and FI frequency
reference and run command from control circuit terminals) prior to ship-
ment. Multi-function contact inputs from control circuit terminals S3 to
S6 are enabled in both operation modes.
·LOCAL: Both frequency reference and run command are set
by the digital operator. Remote SEQ and REF LEDs
go OFF.
·REMOTE:Master frequency reference and run command can
be selected as described in the table below.
Parameter n111, LOC/REM Change, will determine if the inverter will
acknowledge a previously closed run input during a switchover from
LOCAL to REMOTE mode.
·When n111 is set to “Cycle Extern Run”, the inverter will not start
if the run input is closed during the transition from LOCAL to
REMOTE.
·When n111 is set to “Acept Extern Run”, the inverter will immedi-
ately start if the run input is closed during the transition from
LOCAL to REMOTE.
Operation Mode Selection
LED
Display
LCD
Display
Operation Method Selection
SEQ
LED
Reference Selection
REF
LED
0 SEQ=OPR REF=OPR Operation by run command
from digital operator
OFFMaster frequency reference
from digital operator
OFF
1 SEQ=TRM REF=OPR Operation by run command
from control circuit terminal
ON Master frequency reference
from digital operator
OFF
2 SEQ=OPR REF=TRM Operation by run command
from digital operator
OFFMaster frequency reference
from control circuit terminals
FV and FI
ON
3 SEQ=TRM REF=TRM Operation by run command
from control circuit terminal
ON Master frequency reference
from control circuit terminals
FV and FI
ON
4 SEQ=OPR REF=COMOperation by run command
from digital operator
OFFMaster frequency reference
set by serial communication
ON
5 SEQ=TRM REF=COM Operation by run command
from control circuit terminal
ON Master frequency reference
set by serial communication
ON
6 SEQ=COM REF=COMOperation by run command
from serial communication
ON Master frequency reference
set by serial communication
ON
7 SEQ=COM REF=OPROperation by run command
from serial communication
ON Master frequency reference
from digital operator
OFF
8 SEQ=COM REF=TRM Operation by run command
from serial communication
ON Master frequency reference
from control circuit terminals
FV and FI
ON