User`s manual

44 FP5/GP5 User’s Manual
n037
Multi-function input 2
(Terminal S3 Sel)
Set items are same as n036.
(When n036=”FWD/REV Cmd (3W), “In Use By
Other” is displayed, and setting is prohibited)
Ext
Fault
(NO)
78
n038Multi-function input 3
(Terminal S4 Sel)
Set items are same as n036. Fault
Reset
78
n039
Multi-function input 4
(Terminal S5 Sel)
Set items are same as n036.
(When n040=”Up/Down Control, “In Use By Other
is displayed, and setting is prohibited)
Multi-
Step
Spd 1
78
n040Multi-function input 5
(Terminal S6 Sel)
Set items are same as n036.
LED
Setting LCD Setting Description
29 Up / Down controlUp / Down command (Terminal
S5=Up command, and terminal
S6=Down command).
Multi-
Step
Spd 2
78
n041Multi-function output
selection 1
(Terminal MA Sel)
LED
Setting LCD Setting Description
0 Fault Fault
1 During Running During running
2 At Speed Frequency agree
3 At Desired Speed Desired frequency agree
4 Freq Detection 1 Frequency detection 1
5 Freq detection 2 Frequency detection 2
6 OverTrq Det (NO) Over/Undertorque detection (nor-
mally open)
7 OverTrq Det (NC) Over/Undertorque detection (nor-
mally closed)
8 Baseblocked During baseblock
9 Operation Mode Local mode
10 Ready Inverter operation ready
11 Timer Output Timer function
12 Auto-Restarting During auto restart
13 OL Pre-Alarm OL pre-alarm (80% OL1 or OL2)
14 Freq Ref Loss Frequency reference loss
15 Set By COM Cntl Closed by serial communication
16 PID Fdbk Loss PID feedback loss
17 OH1 Alarm OH1 Alarm (set if n035 set to "3")
Fault 83
n042Multi-function output
selection 2
(Terminal M1 Sel)
Set items are as same as n041 During
Running
83
n043Master analog input selec-
tion - FV or FI terminal
(Analog Input Sel)
LED LCD
Setting
Setting FV FI Remarks
0 FV=MSTRFI=AUX Master Aux. Enable
1 FV=AUX FI=MSTRAux. Master Enable
2 FV=RST FI=MSTRFault resetMaster Disable
Enable: FV/FI switchover function is enabled.
Disable: FV/FI switchover function is disabled.
Note: When PID is enabled (n084 0),
FV terminal = PID reference, and
FI terminal = PID feedback.
FV=MSTR
FI=AUX
82
n044
Aux. analog input
selection
(Terminal FI Sel)
LED
Setting LCD Setting Description
0 0-10VDC 0~10V input (Jumper J1 must be cut)
1 4-20mA 4~20mA input
4-20mA 82
n045Frequency reference
retention
(MOP Ref Memory)
LED
Setting LCD Setting Description
0 Memorize Fref Retained in frequency reference 1 (n024)
1 Not MemorizedNot retained after power-down
Memorize
Fref
82
n046
Operation method for
frequency reference
loss detection
(Ref Loss Detect)
LED
Setting LCD Setting Description
0 Not detected No detection
1 Run @ n047 Fref Continue to run at n047 setting
Not
Detected
82
No. Function Name
(LCD Operator Display)
Description Factory
Default
User
Setting
Ref.
Page
Chapter 3 - Programming Features
FP5/GP5 Parameters