FP5/GP5 User’s Manual 57
Frequency Agree Set Point (n075, Freq Det Level)
When multi-function contact output selections n041 or n042 are set to “Freq
Det 1” or “Freq Det 2”, frequency detection is enabled. This function is acti-
vated when the output frequency is above or below the frequency agree set
point (n075).
·Output frequency Frequency agree set point
Set n041 or n042 to “Freq Det 1”.
·Output frequency Frequency agree set point
Set n041 or n042 to “Freq Det 2”.
ON ON
Release Width
+2Hz
Output Frequency
Frequency Detection
Signal
Frequency Agree Set Point
n075
Figure 26 Frequency Agree Set Point Example
(Fout
Frequency Agree Set Point)
ON
Release Width
-2Hz
Output Frequency
Frequency Detection
Signal
Frequency Agree Set Point
n075
Figure 27 Frequency Agree Set Point Example
(Fout Frequency agree set point)
Chapter 3 - Programming Features
FP5/GP5Operation