Chapter 3 - Programming Features
FP5/GP5 Operation
Stopping Method (n004, Stopping Method)
This function selects the stopping method suitable for the particular application.
·Deceleration to Stop (n004 = “Ramp to STOP”)
Upon removal of the FWD (REV) run command, the motor decelerates at
a deceleration rate determined by the time set in deceleration time 1
(n019) and DC injection braking is applied immediately before when the
minimum output frequency (n016) is reached. If the deceleration time is
short or the load inertia is large, an overvoltage fault (OV) may occur dur-
ing deceleration. In this case, increase the deceleration time or install an
optional braking resistor .
Braking torque:w/o braking resistor, approx. 20% of motor rated torque
w/ braking resistor, approx. 150% of motor rated torque
·Coast to Stop (n004 = “Coast to STOP”)
Upon removal of the FWD (REV) run command, the motor coasts.
LED Setting LCD Setting Description
0 Ramp to STOP Deceleration to stop (factory default)
1 Coast to STOP Coast to stop
2 Coast w/Timer 1Coast to stop with timer 1 (run command cycle)
3 Coast w/Timer 2Coast to stop with timer 2 (auto-start after time out)
Output Frequency
Decel time 1 (n019)
Run Command
ON
OFF
DC injection Braking Time
at Stop (n069)
Factory Default: 0.5 s
DC Injection Braking Start - n016)
Factory Default: 1.5Hz
Min. Output Frequency (Frequency at
Figure 39 Stopping Method - Deceleration to Stop
Run command
ON
OFF
Output frequency
Inverter output is shut OFF
when stop command is given.
Figure 40 Stopping Method - Coast to Stop