Chapter 3 - Programming Features
Inputs & Outputs
* For 460V class units, the value is twice that of 230V class units.
Increasing the voltage in the V/f pattern increases motor torque, how-
ever, an excessive increase may cause:
· Inverter fault trips as a result of motor overexcitation
· Motor overheat or excessive vibration
Increase voltage gradually while checking the motor current.
Parameter
No.
Name Unit Setting Range
Factory
Default
(n010=60Hz
Preset)
Factory
Default
(n010=User
defined V/f)
n011 Maximum output frequency 0.1 Hz50.0 to 400 Hz 60.0 Hz 60.0 Hz
n012 Maximum voltage 0.1 V 0.1 to 255 V * 230 V * 230 V *
n013 Maximum voltage output fre-
quency (base frequency)
0.1 Hz 0.2 to 400 Hz 60.0 Hz 60.0 Hz
n014 Mid. output frequency 0.1 Hz0.1 to 399.9 Hz 3.0 Hz 30.0 Hz
n015 Mid. output frequency voltage0.1 V 0.1 to 255 V * 17.2 V * 57.5 V *
n016 Minimum output frequency 0.1 Hz0.1 to 10.0 Hz 1.5 Hz 1.5 Hz
n017 Minimum output frequency
voltage
0.1 V 0.1 to 50.0 V * 11.5 V * 11.5 V *
Be sure to satisfy the following
conditions for setting parameters
n011 to n017:
n016 n014 < n013 n011
0
n016n014
n013 n011
Frequency
Voltage
n017
n015
n012
Figure 46 Custom V/f Pattern Setting