Control Characteristics
Control Method Sine wave PWM with full-range, automatic torque boost
Frequency Control
Range
0.1 to 400 Hz
Frequency Accuracy Digital command: 0.01%, Analog command: 0.1%
Frequency Setting Reso-
lution
Digital Operator Reference: 0.1Hz,
Analog Reference: 0.06Hz (@60Hz)
Output Frequency Reso-
lution
0.01 Hz
Frequency Setting 0 to +10VDC (20k), 4-20mA (250)
Accel/Decel Time
0.0 to 3600.0 sec.
(Accel/Decel time setting independently: 0.1 sec )
Braking Torque Approx. 20%
No. of V-f Patterns 1 preset V/f pattern and 1 custom pattern
Protective Functions
Motor Overload Protec-
tion
Electronic thermal overload relay (I
2
T)
Instantaneous Overcur-
rent
Motor coasts to stop at approx. 200% rated output current.
Fuse Protection Motor coasts to stop at blown fuse.
Overload Motor coasts to stop after 1 min. at rated overload capacity.
Overvoltage
Motor coasts to a stop if converter output voltage exceeds 410VDC
(820VDC at 460V input)
Undervoltage
Motor coasts to stop if converter output voltage drops below user
adjustable value
Momentary Power Loss
Immediate stop after 15 ms or longer power loss. (Continuous system opera-
tion during power loss less than 2 sec is equipped as standard.)
Heatsink Overheat Thermistor - OH1, OH2
Stall Prevention
Stall prevention at acceleration/deceleration and constant speed
operation
Ground Fault Provided by electronic circuit
Power Charge Indication Charge LED stays on until voltage drops below 50VDC
Input Phase Loss Single-phase protection
Environmental Conditions
Location Indoor (protected from corrosive gases and dust)
Ambient
Temperature
+14 to 104°F (-10 to 40°C) for NEMA 1 type (not frozen)
+14 to 113°F (-10 to 45°C) for open chassis type
Storage
Temperature
-4 to 140°F (-20 to 60°C)
Humidity 95% RH (non-condensing)
Vibration
9.8m/s
2
(1G) less than 20Hz, up to 1.96m/s
2
(0.2G) at 20 to 50Hz