Chapter 3 - Programming Features
Inputs & Outputs
·Up/Down Command (setting: n040 = “Up/Down Control”)
With the FWD (REV) run command entered, a change in frequency is
performed by inputting the Up or Down commands to control circuit
terminals S5 and S6, so that operation can be performed at the desired
speed. When the Down command is specified for terminal S6 by setting
n040=”Up/Down Control”, any function set to terminal S5 via parameter
n039 becomes disabled; terminal S5 becomes an input terminal for the
Up command and terminal S6 an input terminal for the Down command.
Notes:
1)When the UP/DOWN command is selected, the upper limit speed is set regardless of fre-
quency reference.
Upper limit speed =Maximum output frequency (n011)
× Frequency reference upper limit (n031) /100
2)The lower limit value is either the analog frequency from control circuit terminals FV or
FI, or the frequency reference lower limit (n032), whichever is larger.
3)When the FWD (REV) run command is input, operation starts at the lower limit speed
without an UP/DOWN command.
4)If the jog frequency reference is input while the drive is running by the UP/DOWN
command, the jog frequency reference has priority.
Control Circuit Terminal S5 (UP command) Closed Open Open Closed
Control Circuit Terminal S6 (DOWN command) Open Closed Open Closed
Operation Status Accel Decel Hold Hold
Figure 50 Timing Diagram of UP/DOWN Command Input
FWD Run
UP Command S5
DOWN Command S6
Upper Limit Speed
Lower Limit Speed
Output Frequency
Frequency Agree Signal
DHU U1D1 D1D D DH H H H HU UH
U: Up (accelerating) status
D: Down (decelerating) status
H: Hold (constant speed) status
UI: Up status, with clamping at upper limit speed
DI: Down status, with clamping at lower limit speed