4.1 MAINTENANCE & INSPECTION
This section describes basic maintenance and inspection procedures for
the FP5/GP5.
Periodic Inspection
The FP5/GP5 will function longer if it is kept clean, cool and dry,
and if all precautions highlighted in this manual are observed. Periodi-
cally inspect the inverter as described in the table below to prevent acci-
dents and to ensure high performance with high reliability.
To prevent electrical shock, disconnect all power before servicing the
inverter. Then wait at least five minutes after the power supply is discon-
nected and all LEDs are extinguished.
Parts Replacement Schedule
Replace the following parts periodically, for long, safe, trouble-free oper-
ation of the FP5/GP5:
Component Check Corrective Action
External Terminals,
Connectors, Mounting
Screws, etc.
Loose screws or connectors Securely tighten.
Heatsink Build-up of dust and dirt
Blow with dry, compressed air [39.2
× 10
4
to 58.8 × 10
4
Pa (4 to 6kg·cm
2
)
pressure].
Printed Circuit Board
(PCB)
Accumulation of conductive dust or
oil
Blow with dry, compressed air [39.2
× 10
4
to 58.8 × 10
4
Pa (4 to 6kg·cm
2
)
pressure]. If dust and oil cannot be
removed, replace the board.
Cooling Fan For abnormal noise and vibration Replace the cooling fan.
Power Components Accumulation of dust and dirt
Blow with dry, compressed air [39.2
× 10
4
to 58.8 × 10
4
Pa (4 to 6kg·cm2)
pressure].
Smoothing CapacitorDiscoloration or odor Replace the capacitor or the inverter.
Parts Approximate Interval Remarks
Cooling Fan 2 to 3 years Replace with new one.
Smoothing Capacitor 5 years Replace with new one (after inspection).
Breakers or Relays -- Decide after inspection.
Fuses 10 years Replace with new one.
Aluminum Electrolytic
Capacitor on PCB Board
5 years Replace with new one (after inspection).