Product specifications

Troubleshooting
44 Samsung Electronics
4-3-3
: Error due to abnormal data of Water outlet thermistor value
t Water outlet thermistor has a defective OPEN/SHORT
t Refer to how to determine below
Wired remocon display
Criteria
Cause of problem
Outdoor unit display
x x x
(
x x x
:
The address of the error occurred indoor unit)
No
Re-start after put the connetor in the PBA.
Yes
1. How to check
After putting out the thermistor
from the PBA Measure its resistance
value B/W two terminal.
The thermistor needs to be replaced.
No
Is the resistance value
Deviated from the temp. table,
significantly?
Yes
Re-start after replacing PBA.
Temperature
(°C)
Resistance
(KΩ)
70
60
50
40
30
21
10
0
-10
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Does Water outlet
thermistor connector
come out of the PBA?
Ex) In case of 26°C – its resistance : around 10.93KΩ