Instruction manual

Page 11 of 100 Report No. 255837
TRF No. IEC60335_2_40F
Test item particulars .................................................. : Air-conditioner
Classification of installation and use ............................ : Fixed / Stationary appliance / Built-in duct type
Supply Connection ....................................................... : Type Y attachment
...................................................................................... :
...................................................................................... :
Possible test case verdicts:
- test case does not apply to the test object ................. : N/A
- test object does meet the requirement ....................... : P (Pass)
- test object does not meet the requirement ................. : F (Fail)
Testing .......................................................................... :
Date of receipt of test item ............................................ : 2014-02-04
Date (s) of performance of tests ................................... : 2014-02-05 to 2014-03-15
General remarks:
The test results presented in this report relate only to the object tested.
This report shall not be reproduced, except in full, without the written approval of the Issuing testing
laboratory.
"(See Enclosure #)" refers to additional information appended to the report.
"(See appended table)" refers to a table appended to the report.
Throughout this report a comma is used as the decimal separator.
General product information:
1) This test report is for the models of indoor unit as following;
a) AM056FNLDEH; b) AM045FNLDEH; c) AM036FNLDCH; d) AM028FNLDCH; e) AM022FNLDCH
2) The variant models, AM045FNLDEH; AM036FNLDCH; AM028FNLDCH; AM022FNLDCH are same as the
model AM056FNLDEH just except for the electrical rating by the difference of outdoor unit which is
connected with indoor unit.
3) Each model has different rated cooling/ heating capacity for the outdoor unit which is combined with the
indoor unit.
4) This appliance is not considered having any IP degrees, i.e. IPX0.
5) This appliance is not intended to be installed where accessible to the general public, which is intended to
be maintained by qualified service personnel and located at a level not less than 2,5m.
6) This test report is just for the indoor unit, and the indoor unit/ outdoor unit shall be installed by a service
agent or similarly qualified persons with an end user’s preference with the combination specified by
manufacturer.