Page 12 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
5 GENERAL CONDITIONS FOR THE TESTS
Tests performed according to cl. 5, e.g. nature of
supply, sequence of testing, etc.
All the tests are conducted
according to this standard.
P
5.2
If the test of annex D has to be carried out, an
additional appliance may be used (IEC 60335-1/A1)
Not applicable. N/A
Tests of clause 21 carried out on separate samples.
Tests of clauses 11, 19 and 21 require pressure
measurements made at various points in
refrigerating system (IEC 60335-2-40/A1)
Performed according to the
requirement.
P
At least one additional specially prepared sample
required for tests of annex FF (Leak simulation tests)
(IEC 60335-2-40/A1)
P
Temperatures on refrigerant piping measured during
test of clause 11 (IEC 60335-2-40/A1)
Tested as this clause.
P
5.3
The tests of clause 14 and 21.2 and 22.24 are
carried out after the tests of clause 29
(IEC 60335-1/A1)
Not applicable. N/A
5.6
Appropriate controls rendered inoperative during test
(IEC 60335-2-40)
Tested as this clause. P
5.7
Tests of clauses 10 and 11 carried out under most
severe operating conditions within operating
temperature range specified by manufacturer.
Annex AA provide examples of such temperature
conditions (IEC 60335-2-40)
Annex AA: A7 A20.
Also considered ISO 13253
and ISO 15042.
P
5.10
For split-package units, refrigerant lines installed in
accordance with installation instructions
(IEC 60335-2-40)
Provide with indoor unit and
outdoor unit in separate.
Installed as its instructions.
P
Refrigerant line length is maximum length stated in
installation instructions or (IEC 60335-2-40)
N/A
7,5 m, whichever is shorter (IEC 60335-2-40) 7,5 m P
Thermal insulation of refrigerant lines applied in
accordance with installation instructions
(IEC 60335-2-40)
Applied as instructions. P
5.14
NOTE: Guidance is given in annex P for enhanced
requirements that may be used to ensure an
acceptable level of protection against electrical and
thermal hazards for particular types of appliances
used in an installation without a protective earthing
conductor in countries that have warm damp
equable climates (IEC 60335-1/A1)
Not applicable. N/A