Page 20 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
8.1.2
Use of test probe 13 of IEC 61032 through openings
in class 0 appliances and class II appliances/
constructions: no contact with live parts
Class I appliance. N/A
Test probe 13 also applied through openings in
earthed metal enclosures having a non-conductive
coating: no contact with live parts
N/A
8.1.3
For appliances other than class II, use of test
probe 41 of IEC 61032: no contact with live parts of
visible glowing heating elements
No visible glowing heating
elements.
N/A
8.1.4 Accessible part not considered live if:
- safety extra-low a.c. voltage: peak value not
exceeding 42,4 V
Adequately protected. N/A
- safety extra-low d.c. voltage: not exceeding 42,4 V
N/A
- or separated from live parts by protective
impedance
N/A
If protective impedance: d.c. current not exceeding
2 mA, and
N/A
a.c. peak value not exceeding 0,7 mA
N/A
- for peak values over 42,4 V up to and including
450 V, capacitance not exceeding 0,1 µF
N/A
- for peak values over 450 V up to and including
15 kV, discharge not exceeding 45 µC
N/A
The quantity of electricity in the discharge is
measured using a resistor having a nominal
non-inductive resistance of 2000 Ω
(IEC 60335-1/A1)
N/A
- for peak values over 15 kV energy of discharge not
exceed 350 mJ (IEC 60335-1/A2)
N/A
8.1.5 Live parts protected at least by basic insulation before installation or assembly:
- built-in appliances
Intended for built-in use. P
- fixed appliances
Fixed appliance. P
- appliances delivered in separate units
Intended to be delivered as
separate units: Indoor unit and
outdoor unit.
P
8.2
Class II appliances and constructions constructed so
that there is adequate protection against accidental
contact with basic insulation and metal parts
separated from live parts by basic insulation only
Class I appliance. N/A
Only possible to touch parts separated from live
parts by double or reinforced insulation
Class I appliance. N/A