TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement – Test Result Verdict
10 POWER INPUT AND CURRENT
—
10.1
Power input at normal operating temperature, rated
voltage and normal operation not deviating from
rated power input by more than shown in table 1
(See appended table)
P
Deviation of appliance with one or more rated
voltage ranges (IEC 60335-1/A2)
Rated: 220 – 240 V or
208 – 230 V
Measured at arithmetic mean
value of the rated voltage
range.
P
10.2
Current at normal operating temperature, rated
voltage and normal operation not deviating from
rated current by more than shown in table 2
(See appended table)
P
Deviation of appliance with one or more rated
voltage ranges (IEC 60335-1/A2)
Rated: 220 – 240 V or
208 – 230 V.
Measured at arithmetic mean
value of the rated voltage
range.
P
11 HEATING
—
11.1
No excessive temperatures in normal use
(IEC 60335-2-40)
No excessive temperatures. P
Compliance is checked by the tests of annex C, if (IEC 60335-2-40): —
- temperature of motor winding exceeds values
shown in table 3 (IEC 60335-2-40)
Not exceeded. N/A
- there is doubt about classification of insulation
system of the motor (IEC 60335-2-40)
No doubt about the
classification of insulation
system of motors.
N/A
11.2 Placing and mounting of appliance (IEC 60335-2-40): —
- clearances to adjacent surfaces (IEC 60335-2-40);
Installed in accordance to the
manual.
P
- flow rates for liquid source or sink equipment be
minimum, except for fan coils where flow rates and
liquid temperatures be maximum
(IEC 60335-2-40/A2);
No means for adjustment. N/A
- static pressures (IEC 60335-2-40);
N/A
- means of adjusting the flow, flow for tests be
minimum obtainable (IEC 60335-2-40);
N/A
- adjustable limit controls set at maximum cut-out
setting and minimum differential (IEC 60335-2-40).
No adjustable limit controls. N/A
Appliances with supplementary heaters, use test
casing of clause 11.9 (IEC 60335-2-40)
No supplementary heaters. N/A
11.2.1
Appliances with supplementary heaters, inlet duct
connected to inlet air opening (IEC 60335-2-40)
No supplementary heaters. N/A