TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
Leakage current measurements (IEC 60335-2-40) (See appended table)
P
13.3
Appliance disconnected from supply and insulation is
immediately subjected to voltage having frequency
of 50 Hz or 60 Hz for 1 min, in accordance with
IEC 61180-1 (IEC 60335-1/A1)
Applied test voltages to each
insulation as specified.
P
High-voltage source used for test is to be capable of
supplying short circuit current Is between the output
terminals after output voltage adjusted to appropriate
test voltage (IEC 60335-1/A1)
(See appended table)
P
Overload release of circuit is not to be operated by
any current below tripping current Ir. Values of Is and
Ir given in table 5 for various high-voltage sources
(IEC 60335-1/A1)
(See appended table)
P
No breakdown during the tests
No breakdown. P
14 TRANSIENT OVERVOLTAGES
Appliances withstand the transient overvoltages to
which they may be subjected
Not applicable. N/A
Clearances having a value less than specified in
table 16 subjected to an impulse voltage test, the
test voltage specified in table 6
N/A
No flashover during the test, unless of functional
insulation
N/A
In case of flashover of functional insulation, the
appliance complies with clause 19 with the clearance
short circuited
N/A
15 MOISTURE RESISTANCE
15.1
Enclosure provides degree of moisture protection
against ingress of water (rain, overflow from drain
pan or defrosting), tests of clause 15.2, 15.3, 11.6
and 16) (IEC 60335-2-40)
IPX0 for indoor unit.
Adequately prevented from
spillage of liquid and overflow
which may reduce clearances
and creepage distances.
P
Motor-compressor not operated and detachable
parts removed during tests of clause 15.2 and 15.3
(IEC 60335-2-40/A2)
P
15.2
Tests in accordance with IEC 60529 in appliances
other than IPX0, as specified (IEC 60335-2-40) ..... :
IPX0 for indoor unit. N/A
15.3
Drain pan filled to brim and subjected to continuous
overflow and fan(s) switched on (IEC 60335-2-40)
Adequately prevented from
spillage of liquid and overflow
which may reduce clearances
and creepage distances.
P