Instruction manual

Page 24 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
15.101 Spillage test as specified (IEC 60335-2-40/A2)
Not accessible to the general
public.
Described on the installation
manual it shall be installed at a
level of 2,5 m above the floor
or grade level.
N/A
After spillage completed, appliance withstand test of
clause 16 (IEC 60335-2-40/A2)
N/A
16 LEAKAGE CURRENT AND ELECTRIC STRENGTH
16.1
Leakage current not excessive and electric strength
adequate
P
Protective impedance disconnected from live parts
before carrying out the tests
P
16.2
Single-phase appliances: test voltage 1,06 times
rated voltage ............................................................. :
1,06 x 240V~ 50/60Hz P
Three-phase appliances: test voltage 1,06 times
rated voltage divided by 3 ...................................... :
N/A
Leakage current measurements (IEC 60335-2-40) (See appended table)
P
16.3 Electric strength tests according to table 7 (See appended table)
P
No breakdown during the tests
No breakdown. P
17 OVERLOAD PROTECTION OF TRANSFORMERS AND ASSOCIATED CIRCUITS
No excessive temperatures in transformer or
associated circuits in event of short-circuits likely to
occur in normal use
N/A
Appliance supplied with 1,06 or 0,94 times rated
voltage and the most unfavourable short-circuit or
overload likely to occur in normal use applied ........ :
N/A
Temperature rise of insulation of the conductors of
safety extra-low voltage circuits not exceeding the
relevant value specified in table 3 by more than 15 K
N/A
Temperature of the winding not exceeding the value
specified in table 8,
N/A
however limits do not apply to fail-safe transformers
complying with sub-clause 15.5 of IEC 61558-1
N/A
19 ABNORMAL OPERATION
19.1
The risk of fire or mechanical damage under
abnormal or careless operation obviated (tests 19.2-
19.14) (IEC 60335-2-40)
P
Failure of transfer medium flow or of any control
device not result in a hazard (IEC 60335-2-40)
P