IEC 60335-2-40
Clause Requirement Test Result Verdict
Electronic circuits so designed and applied that a
fault will not render the appliance unsafe (electric
shock, fire or mechanical hazard, dangerous
malfunction) (test 19.11 and 19.12)
(IEC 60335-2-40)
P
19.2
Test of appliance with motor rotors, other than
motor-compressors, operated for 15 days (360 h) or
until protection device opens circuit
(IEC 60335-2-40)
Fan motor for indoor unit.
Thermally protected.
P
Insulation of motor windings (IEC 60335-2-40) ....... :
Cl. B (Cl. 130) P
Temperature of enclosure does not exceed (°C)
(IEC 60335-2-40)...................................................... :
Indoor fan motor:
- YSK110-50-4SM: 80.1 °C
Results: Less than 150 °C.
No hazard.
P
Temperature of the windings does not exceed the
values shown in the table ; temperature (°C)
(IEC 60335-2-40)...................................................... :
Indoor fan motor:
- YSK110-50-4SM: 139.5 °C
Results: Less than the values
specified.
No hazard.
P
Electric strength test as specified in 16.3, 72 h after
the beginning of the test (IEC 60335-2-40)
Between windings and
enclosure: 1250V for 1min
P
30 mA residual current device does not open
(IEC 60335-2-40)
P
At the end, leakage current between windings and
enclosure does not exceed 2 mA (IEC 60335-2-40)
Measured: 0.61mA
Less than 2mA
P
19.3
Motor-compressor complies with IEC 60335-2-34
(IEC 60335-2-40)
Not checked in the appliance. N/A
Test of motor-compressor with rotor locked as
specified in clause 19.101 of IEC 60335-2-34 and
comply with 19.104 of that standard
(IEC 60335-2-40)
N/A
19.4
Test of three-phase motors operated under
conditions of clause 11 with one phase disconnected
until steady conditions or protective device operates
(IEC 60335-2-40)
N/A
19.5
Test of appliance with heat transfer medium flow of
the outdoor heat exchanger restricted or shut off
when reaching steady conditions (IEC 60335-2-40)
(see appended table)
Results: No hazard.
No severe temperature rise.
P
Test of appliance with heat transfer flow of the indoor
heat exchanger restricted or shut off when reaching
steady conditions (IEC 60335-2-40)
(see appended table)
Results: No hazard.
No severe temperature rise.
P
Disconnection of motor common to both the outdoor
and the indoor heat exchangers when reaching
steady conditions (IEC 60335-2-40)
N/A
19.6
Test of appliances using water as heat transfer
medium (IEC 60335-2-40)
Not such an appliance. N/A