Page 28 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
PTC’s, NTC’s and VDR’s resistors not short-circuited
if used as specified by manufacturer
(IEC 60335-2-40)
P
19.12
If safety of appliance for any of fault conditions
specified in clause 19.11.2 depends on operation of
miniature fuse-link complying with IEC 60127, test
repeated with fuse-link replaced by an ammeter
(IEC 60335-2-40)
P
Current 2,1 times rated current of fuse-link, circuit
not adequately protected (fuse-link short-circuited)
(IEC 60335-2-40)
N/A
Current 2,75 times rated current of fuse-link, circuit
adequately protected (IEC 60335-2-40)
Rated (F100): 250V~ T5A
During testing, F100 broken at
118 A (> 2.75 x 5A)
Considered as adequately
protected.
P
Current 2,1 and 2,75 times rated current,
fuse-link short-circuited and test carried out during
specified time (IEC 60335-2-40)
N/A
19.13
Appliances with PTC heating elements test as
specified (IEC 60335-2-40)
No PTC heating elements. N/A
19.14
During tests of clause 19.2 to 19.10.101 and 19.11,
19.12 and 19.13 if appropriate, appliances not emit
flames, molten metal, poisonous or ignitable gas in
hazardous amounts (IEC 60335-2-40/A2)
No flames, molten metal,
poisonous or ignitable gas in
hazardous amounts.
P
Enclosures not deform (IEC 60335-2-40)
P
Temperature rise not exceed values shown in table
9
(IEC 60335-2-40)
(See appended table)
P
Electric strength test, test voltage as specified in
table 4 (IEC 60335-2-40)
No breakdown. P
19.101
All appliances provided with supplementary heaters
and free air discharge subjected to specified test in
each mode of operation (IEC 60335-2-40/A2)
No supplementary heaters. N/A
During test temperature not exceed 150 °C but an
overshoot of 25 °C is permitted during first hour
(IEC 60335-2-40/A2)
No supplementary heaters. N/A
20 STABILITY AND MECHANICAL HAZARDS
20.1 Adequate stability
Fixed appliance. N/A
Tilting test through an angle of 10 ° (appliance
placed on an inclined plane/horizontal plane);
appliance does not overturn
N/A
Tilting test repeated on appliances with heating
elements, angle of inclination increased to 15 °
N/A