Instruction manual

Page 29 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
Possible heating test in overturned position;
temperature rise does not exceed values shown in
table 9
N/A
20.2
Moving parts adequately arranged or enclosed as to
provide protection against personal injury
Adequately arranged and
protected.
P
Protective enclosures, guards and similar parts are
non-detachable
P
Adequate mechanical strength and fixing of
protective enclosures
P
Self-resetting thermal cut-outs and overcurrent
protective devices not causing a hazard, by
unexpected reclosure
No hazard. P
Not possible to touch dangerous moving parts with
test probe
No touch with test probe.
Described to be installed at a
level of 2,5 m height on manual
as well.
P
21 MECHANICAL STRENGTH
21.1
Appliance has adequate mechanical strength and
constructed as to withstand rough handling
Having adequate mechanical
strength.
P
Checked by applying blows to the appliance in
accordance with test Ehb of IEC 60068-2-75, spring
hammer test, impact energy 0,5 J (IEC 60335-1/A1)
Providing with adequate
mechanical strength.
P
If necessary, supplementary or reinforced insulation
subjected to the electric strength test of 16.3
No doubt, no needs. N/A
If necessary, repetition of groups of three blows on a
new sample
No doubt, no needs. N/A
Safety requirements specified in annex EE applied.
Pressure test in annex EE applies to parts other than
pressure vessels (IEC 60335-2-40/A1)
1) Motor-compressor is not
applicable in this test report.
2) Test location:
Heat exchanger of indoor unit.
Test result:
No leakage, damage, or
hazard.
P
Safety requirements of ISO 5149 applied
(IEC 60335-2-40/A2)
Complying with ISO 5149. P
21.2
Accessible parts of solid insulation shall have
sufficient strength to prevent penetration by sharp
implements (IEC 60335-1/A1)
P
Compliance is checked by subjecting the insulation
to the following test, unless the thickness of
supplementary insulation is at least 1 mm and that of
reinforced insulation is at least 2 mm
(IEC 60335-1/A1)
1) Supplementary insulation:
Not less than 1mm
2) Reinforced insulation:
Not less than 2mm
P