Page 37 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
Manual setting and visual indication not necessary on appliances that can operate as
follows, without giving rise to a hazard (IEC 60335-1/A2):
- operate continuously (IEC 60335-1/A2),
N/A
- operate automatically, or (IEC 60335-1/A2)
N/A
- be operated remotely (IEC 60335-1/A2)
N/A
22.52
Socket-outlets on appliances accessible to user in
accordance with socket-outlet system used in
country where appliance sold (IEC 60335-1/A2)
No socket-outlets. N/A
22.101
Appliances intended to be fixed, securely fixed
(IEC 60335-2-40)
Securely fixed. P
22.102.1
At least two thermal cut-outs in appliances with
supplementary heating elements for air (first one be
self-resetting and other non-self-resetting thermal
cut-out) (IEC 60335-2-40/A2)
No supplementary heating
elements.
N/A
22.102.2
Appliances provided with supplementary heaters for
water incorporate non-self-resetting thermal cut-out,
providing all-pole disconnection that operates
separately from water thermostats
(IEC 60335-2-40/A2)
No supplementary heaters. N/A
However, for appliances intended to be connected to
fixed wiring, the neutral conductor need not be
disconnected (IEC 60335-2-40/A2)
N/A
22.102.3
Thermal cut-outs of capillary type open in event of
leakage from capillary tube (IEC 60335-2-40/A2)
No supplementary heaters. N/A
22.103
Non-self-resetting cut-outs independent of other
control devices (IEC 60335-2-40)
N/A
22.104
Containers of sanitary hot water heat pumps
withstand twice permissible operating pressure in
closed containers (IEC 60335-2-40) or
No sanitary hot water heat
pumps.
N/A
0,15 MPa in open containers (IEC 60335-2-40)
N/A
without leakage or rupture (IEC 60335-2-40)
N/A
22.105
Air or vapour cushion in closed containers not
exceeding 10 % (IEC 60335-2-40)
Not provided. N/A
22.106
Pressure relief devices operating at 0,1 MPa over
permissible operating pressure (IEC 60335-2-40)
Not provided. N/A
22.107
Water outlet systems of open containers free from
obstruction causing over-pressure (IEC 60335-2-40)
Not provided. N/A
Vented containers of sanitary hot water heat pumps
always open to the atmosphere through appropriate
aperture (IEC 60335-2-40)
N/A
22.108
Not vented open containers subjected to test in
accordance with clause 22.104 to vacuum of 33 kPa
for 15 min (IEC 60335-2-40)
No sanitary hot water heat
pumps.
N/A