TRF No. IEC60335_2_40F
Summary of testing:
Tests performed (name of test and test clause):
- Clause 7: Marking and instructions
- Clause 8: Protection against access to live parts
- Clause10: Power input and current
- Clause 11: Heating
- Clause 13: Leakage current and electric strength at
operating temperature
- Clause 15: Moisture resistance
- Clause 16: Leakage current and electric strength
- Clause 19: Abnormal operation
- Clause 20: Stability and mechanical hazards
- Clause 21: Mechanical strength
- Clause 22: Construction
- Clause 23: Internal wiring
- Clause 24: Components
- Clause 25: Supply connection and external flexible
cord
- Clause 26: Terminals for external conductors
- Clause 27: Provision for earthing
- Clause 28: Screws and connections
- Clause 29: Clearances, creepage distances and
solid insulation
- Clause 30: Resistance to heat and fire
- Clause 31: Resistance to rusting
- Annex E: Needle flame test
- Annex N: Proof tracking test
- Annex EE: Pressure test
Testing location:
Samsung Electronics Co., Ltd.
Digital Air-solutions Business Team,
129, Samsung-ro, Yeongtong-gu, Suwon-si,
Gyeonggi-do, 443-742 Korea, Republic of
1. Safety test conditions;
Normal temperature condition was considered as following based on ISO 13253 and ISO 15042;
- For climatic class T1, an appliance was installed with the indoor side subjected to 27°C and the outdoor
side subjected to 35°C for cooling function.
- For climatic class T3, an appliance was installed with the indoor side subjected to 29°C and the outdoor
side subjected to 46°C for cooling function.
- An appliance was installed with the indoor side subjected to 20°C and the outdoor side subjected to 7°C for
heating function.
2. EMF test conditions;
1) Measuring distance (r1): 30 cm
2) Sensor locations: Around
3) Operating conditions: Continuously.
Cooling mode: Lowest cooling, Heating mode: Highest heating
3. In this test report, the model AM056FNLDEH (indoor unit, built-in slim duct type) was mainly tested and
evaluated as a representative by connecting it with the model AM080FXVAGR (outdoor unit) in
combination with the model AM071FNLDEH (indoor unit, built-in slim duct type), AM071FN2DEH (indoor
unit, built-in 2-way cassette type), AM056FNJDEH (indoor unit, named as a console type) and
AM071FNCDEH (indoor unit, named as a ceiling type) under the most severe operating condition specified
by the manufacturer.
4. For the relevant tests, a motor-compressor was equipped with an outdoor unit, which was approved by
NEMKO employing a non-flammable refrigerant of R410A.