Page 46 of 100 Report No. 255837
TRF No. IEC60335_2_40F
IEC 60335-2-40
Clause Requirement Test Result Verdict
Supply cords for outdoor use not lighter than
polychloroprene sheathed flexible cord
(60245 IEC 57) (IEC 60335-2-40)
Interconnection cord for
connecting the indoor unit into
the outdoor unit.
Not lighter than the code
designation as following;
60245 IEC 57 (IEC)
H05RN-F (CENELEC)
P
25.8
Nominal cross-sectional area of supply cords
according to table 11; rated current (A);
cross-sectional area (mm²) ...................................... :
The manufacturer, service
agent or similarly qualified
person should use a proper
cross sectional area of supply
cord and interconnection cord
referring to an installation
manual.
It can be variable with the
user’s selection of combination
of outdoor unit with indoor unit.
P
25.9 Supply cord not in contact with sharp points or edges
No contacts. P
25.10
Green/yellow core for earthing purposes in class I
appliance
Protective earthing conductor
is colored green/yellow.
P
25.11
Conductors of supply cords not consolidated by
lead-tin soldering where they are subject to contact
pressure, unless
N/A
clamping means so constructed that there is no risk
of bad contacts due to cold flow of the solder
N/A
25.12
Moulding the cord to part of the enclosure does not
damage the insulation of the supply cord
N/A
25.13
Inlet opening so shaped as to prevent damage to the
supply cord
Well rounded. P
Unless the enclosure at the inlet opening is of
insulation material, a non-detachable lining or
bushing complying with clause 29.3 for
supplementary insulation provided
N/A
If unsheathed supply cord, a similar additional
bushing or lining is required, unless
N/A
the appliance is class 0
N/A
25.14
Supply cords adequately protected against
excessive flexing
N/A
Flexing test:
- applied force (N) ..................................................... :
N/A
- number of flexings .................................................. :
N/A
The test does not result in:
- short circuit between the conductors
N/A
- breakage of more than 10 % of the strands of any
conductor
N/A