Instruction manual

Page 73 of 100 Report No. 255837
TRF No. IEC60335_2_40F
10.1 TABLE: Power input deviation
1)
P
Input deviation of/at:
P rated
(W)
P measured
(W)
P
(%)
Required P
(%)
Remark
220V~ 50Hz 90 83.24 -7.5 +20 Pass
230V~ 50Hz 90 90.69 +0.8 +20 Pass
240V~ 50Hz 90 96.26 +7.0 +20 Pass
10.2 TABLE: Current deviation
1)
P
Current deviation of/at
I rated
(A)
I measured
(A)
I
(%)
Required I
(%)
Remark
220V~ 50Hz 0.52 0.484 -6.9 +20 Pass
230V~ 50Hz 0.52 0.520 0.0 +20 Pass
240V~ 50Hz 0.52 0.548 +5.4 +20 Pass
supplementary information:
This is for the model of indoor unit, AM045FNLDEH.
1)
Measured maximum value under the test condition as below:
a) for lowest cooling,
- Room temperature, indoor DB/WB (°C): 27 / 19
- Room temperature, outdoor DB/WB (°C): 35 / 24
b) for lowest cooling,
- Room temperature, indoor DB/WB (°C): 29 / 19
- Room temperature, outdoor DB/WB (°C): 46 / 24
c) for highest heating,
- Room temperature, indoor DB/WB (°C): 20 / 15
- Room temperature, outdoor DB/WB (°C): 7 / 6