Instruction manual

Page 78 of 100 Report No. 255837
TRF No. IEC60335_2_40F
11.8 TABLE: Heating test, thermocouples
P
Test voltage (V) ........................................................:
254,4V (=1,06 x 240V) 50Hz
243,8V (=1,06 x 230V) 60Hz
Ambient, t
1
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Ambient, t
2
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 44.1 150
Terminal block 29.1 85
Fuse 30.3 T60
Relay 37.2 Min. T70
X-capacitor 30.2 Min. T85
Choke coil 30.5 105
Electrolytic capacitor 31.6 T85
Switching transformer winding 34.9 110 (Cl. B)
PCB surface 32.7 145
Capacitor for indoor fan motor 29.6 T85
Interconnection cord separation 29.1 75
11.8 TABLE: Heating test, resistance method
P
Test voltage (V) ........................................................:
254,4V (=1,06 x 240V) 50Hz
243,8V (=1,06 x 230V) 60Hz
Ambient, t
1
(°C) ........................................................ : See below.
Ambient, t
2
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Temperature of winding R
1
(Ω) R
2
(Ω) T (°C) Max. T (°C)
Insulation
class
Temp. of indoor fan motor;
- Changzhou Regal Beloit Sinya
Motor (YSK110-50-4SM)
94.8
at 23.0°C
108.5
60.2 *)
120
Class B
(Class 130)
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2)
Test condition: Lowest cooling under the climatic class T3.
*) Cu winding, constant k = 234.5