TRF No. IEC60335_2_40F
16.2 TABLE: Leakage current
P
Single phase appliances: 1,06 x rated voltage ..... : 254,4V (=1,06 x 240V)
Three phase appliances 1,06 x rated voltage
divided by 3: ......................................................... :
-
Leakage current between I (mA) Max. allowed I (mA)
Lines to heat exchanger 0.90
10.0
1)
Lines to metal foil of non-metallic part 0.01 0.25
supplementary information:
1)
The maximum allowed limit can be less than 10mA considering the rated maximum power input based on
the combination of indoor unit and outdoor unit.
- for AM080FXVAGR (outdoor unit); 5.00 kW (cooling, T1) / 5.10 kW (heating)
Required limit: 2mA/kW per each operating mode, but with a maximum value of 10 mA.
This appliance is not intended to be installed where accessible to the general public, but in this test report the
leakage current is limited to the requirement of an appliance which may be accessible to the general public.
16.3 TABLE: Electric strength
P
Test voltage applied between: Voltage (V)
Breakdown
(Yes/No)
Line to heat exchanger of indoor unit (Basic insulation) 1250 No
Line to metallic enclosure of indoor unit (Basic insulation) 1250 No
Line to non-metallic part of indoor unit (Reinforced insulation) 3000 No
supplementary information:
17 TABLE: Overload protection, temperature rise
N/A
Temperature rise of part/at:
T (K) Max. T (K)
-- -- --
-- -- --
supplementary information: