Instruction manual

Page 82 of 100 Report No. 255837
TRF No. IEC60335_2_40F
19.5 TABLE: Abnormal operation
P
Test voltage (V) ........................................................ : 240V 50/60Hz
Ambient, t
1
(°C) ........................................................ : Indoor (DB / WB): 23 / (15)
Outdoor (DB / WB): 23 / (15)
Ambient, t
2
(°C) ........................................................ : Indoor (DB / WB): 23 / (15)
Outdoor (DB / WB): 23 / (15)
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 41.8 150
Terminal block 22.9 -
Fuse 23.2 -
Relay 26.4 -
X-capacitor 23.3 -
Choke coil 23.4 -
Electrolytic capacitor 23.5 -
Switching transformer winding 25.4 200 (Cl. B)
PCB surface 25.1 -
Capacitor for indoor fan motor 23.1 -
Interconnection cord separation 23.2 175
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2) Test condition: Lowest cooling with the air-inlet to heat exchanger of indoor unit being blocked.