Instruction manual

Page 83 of 100 Report No. 255837
TRF No. IEC60335_2_40F
19.5 TABLE: Abnormal operation
P
Test voltage (V) ........................................................ : 240V 50/60Hz
Ambient, t
1
(°C) ........................................................ : Indoor (DB / WB): 23 / (15)
Outdoor (DB / WB): 23 / (15)
Ambient, t
2
(°C) ........................................................ : Indoor (DB / WB): 23 / (15)
Outdoor (DB / WB): 23 / (15)
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 36.5 150
Terminal block 23.2 -
Fuse 24.5 -
Relay 31.6 -
X-capacitor 24.4 -
Choke coil 24.5 -
Electrolytic capacitor 25.7 -
Switching transformer winding 29.3 200 (Cl. B)
PCB surface 27.1 -
Capacitor for indoor fan motor 23.5 -
Interconnection cord separation 23.3 175
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2) Test condition: Lowest cooling with the air-inlet to heat exchanger of outdoor unit being blocked.