19.7 TABLE: Abnormal operation
P
Test voltage (V) ........................................................: 240V 50/60Hz
Ambient, t
1
(°C) ........................................................ :
Indoor (DB / WB): 39 / (29)
Outdoor (DB / WB): 56 / (34)
Ambient, t
2
(°C) ........................................................ :
Indoor (DB / WB): 39 / (29)
Outdoor (DB / WB): 56 / (34)
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 79.9 150
Terminal block 40.5 -
Fuse 40.4 -
Relay 47.1 -
X-capacitor 40.3 -
Choke coil 40.4 -
Electrolytic capacitor 41.5 -
Switching transformer winding 44.5 200 (Cl. B)
PCB surface 42.7 -
Capacitor for indoor fan motor 39.3 -
Interconnection cord separation 40.1 175
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2)
Test condition: Lowest cooling with +10K