Page 85 of 100 Report No. 255837
TRF No. IEC60335_2_40F
19.10 TABLE: Abnormal operation
P
Test voltage (V) ........................................................: 240V 50/60Hz
Ambient, t
1
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Ambient, t
2
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 98.4 150
Terminal block 31.5 -
Fuse 32.5 -
Relay 38.3 -
X-capacitor 32.9 -
Choke coil 33.4 -
Electrolytic capacitor 33.2 -
Switching transformer winding 36.4 200 (Cl. B)
PCB surface 34.6 -
Capacitor for indoor fan motor 30.9 -
Interconnection cord separation 31.1 175
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2)
Test condition:
Lowest cooling with the motor rotor of indoor unit being locked.