Instruction manual

Page 86 of 100 Report No. 255837
TRF No. IEC60335_2_40F
19.10 TABLE: Abnormal operation
P
Test voltage (V) ........................................................: 240V 50/60Hz
Ambient, t
1
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Ambient, t
2
(°C) ........................................................ :
Indoor (DB / WB): 29 / 19
Outdoor (DB / WB): 46 / 24
Thermocouple locations T (°C) Max. T (°C)
Enclosure of indoor fan motor 45.1 150
Terminal block 29.0 -
Fuse 30.3 -
Relay 33.7 -
X-capacitor 30.4 -
Choke coil 30.4 -
Electrolytic capacitor 30.5 -
Switching transformer winding 32.6 200 (Cl. B)
PCB surface 31.6 -
Capacitor for indoor fan motor 29.5 -
Interconnection cord separation 29.2 175
supplementary information:
1) This is for the representative model of indoor unit, AM056FNLDEH in connection with the outdoor unit,
AM080FXVAGR.
2)
Test condition:
Lowest cooling with the motor rotor of outdoor unit being locked.