User Manual

17
ENGLISH
1.
The drain pipe should be installed within 100mm from
the
flexible hose, lift up from 100mm to 550mm and lift
down 20mm or more.
2.
Install horizontal drainpipe with a slope of 1/100 or
moreandfixitbyhangerspaceof1~1.5m.
3.
Install the air vent in the horizontal drainpipe to pre-
vent water flow back to the indoor unit.
You may not need to install it if there were proper
slope in the horizontal drainpipe.
Note
4.
The flexible hose should not be installed upward posi-
tion,
it may cause water flow back to the indoor unit.
5.
Install U-trap at the end of the drainpipe to prevent a
nasty smell to reach the indoor unit.
Drainpipe Connection
Flexible hose
Air vent
300mm or less
Horizontal drainpipe
more than 1/100 slope
100~550mm
or less
1~1.5m
100mm
or more
Ceiling
Hanger
1. Install main air vent at the front of the farthest indoor unit
from the main drain when installed indoor units are more
than 3.
2. You may need to install individual air vent to prevent
water flow back at the top of each indoor unit
drainpipe.
Centralized Drainage
Hanger
Main drainpipe
Individual
air vent
Main air vent
Centralized horizontal drainpipe
(more than 1/100 slope)
550mm or less
1~1.5m
g Flexible hose Installation
Install horizontally
Be horizontal
Indoor
Unit
Flexible hose
Max. allowable axis gap
Max. 20mm
Indoor
Unit
Max. allowable bending
angle
Max. 30˚
Indoor
Unit
Handle with using adhesive not to
block the inside of flexible hose
Connect
to PVC
drain pipe
Connect to
indoor unit
Insulation
PVC
drain pipe
(Apply
adhesive on
the inside)
Insulation
Flexible hose
(Apply adhesive on
the outside)
Silver solder
1. Before wiring work, you must turn off all power source.
2. Indoor unit power should be supplied through the
breaker(MCCB, ELB) separated by the outdoor power.
3. The power cable should be used only copper wires.
4. Connect the power cable{1(L), 2(N)} among the units
within maximum length and communication cable(F1,
F2) each.
5. Connect F3, F4(for communication) when installing
the wired remote Control.
Power and communication cable connection
N L
N L N L N L
ELCB
MCCB+
ELB
V1 V2
Indoor Unit 1
Outdoor
Unit
Wired Remote
Control
220-240V~
ELB : Essential Installation
Ceiling, wall-mounted indoor unit.
Indoor Unit 2 Indoor Unit 3
Indoor Unit 4 Indoor Unit 5 Indoor Unit 6
EEV kit
Selecting compressed ring terminal
Norminal
dimensions
for cable
(mm
2
)
Norminal
dimensions
for screw
(mm)
B D d1 E F L d2 t
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Standard
dimension
(mm)
Allowance
(mm)
Min. Min. Max.
Standard
dimension
(mm)
Allowance
(mm)
Min.
1.5
4 6.6
±0.2 3.4
+0.3
-0.2
1.7 ±0.2 4.1 6 16 4.3
+0.2
0
0.7
4 8
2.5
4 6.6
±0.2 4.2
+0.3
-0.2
2.3 ±0.2 6 6 17.5 4.3
+0.2
0
0.8
4 8.5
4 4 9.5 ±0.2 5.6
+0.3
-0.2
3.4 ±0.2 6 5 20 4.3
+0.2
0
0.9
Specification of electronic wire
Power supply MCCB ELB
Power
cable
Earth
cable
Communication
cable
Max : 242V
Min : 198V
X A
X A, 30mmA
0.1 s
2.5mm
2
2.5mm
2
0.75~1.5mm
2
Decide the capacity of ELB and MCCB by below formula.
The capacity of ELB, MCCB X [A] = 1.25 X 1.1 X ∑Ai
X
: The capacity of ELB, MCCB
Ai : Sum of Rating currents of each indoor unit.
Refer to each installation manual about the rating current of indoor unit.
Decide the power cable specification and maximum length
within 10% power drop among indoor units.
Coef: 1.55
Lk: Distance among each indoor unit[m],
Ak: Power cable specification[mm
2
], ik : Running current of each unit[A]
∑ (
Coef×35.6×Lk×ik
) <
10% of input
voltage[V]
1000×Ak
n
k=1
Wire work