User Manual

23
ENGLISH
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation PAGE MODE
Use of robot
cleaning
Use of external room
temperature sensor
Use of central control FAN RPM compensation
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
0 2
0 Disuse 0 Disuse 0 Disuse
0 Disuse
1
RPM
compensation
1 Use 1 Use 1 Use 2
High ceiling
KIT
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation PAGE Use of drain pump
Use of hot water
heater
Use of electronic
heater
EEV Step when heating
stops
Master / Slave
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
1
0 Disuse 0 Disuse 0 Disuse 0 Default value 0 slave
1 Use
1 Use 1 Use 1
Noise
decreasing
setting
1 master
2
When an
indoor unit
stops, drain
pump will
operate for
3min
Option
Option SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
Explanation PAGE
Use of external
control
Setting the output of
external control
S-Plasma ion Buzzer control
Number of hours using
lter
Remote
Controller
Display
Indication
and Details
Indication Details Indication Details Indication Details Indication Details Indication Details Indication Details
2
0 Disuse 0
Thermo
on
0 Disuse 0
Use buzzer
2 1000 Hour
1
ON/OFF
control
1
Operation
on
1 Use 1
Disuse buzzer
6 2000 Hour
2
OFF
control
3
Window
ON/OFF
control
02 series installation option(Detailed)