Installation manual

Drain Pump Installation (optional)
E-19
ENGLISH
Connect the cable to the electrical component box as shown at the figure.
1
Screw the drain pump to the side of the indoor unit with two screws.
2
Adjust K4 DIP switch(SW03) to the "OFF" position.
3
Wrap the drain tube outlet on the right and left side of
the indoor unit with an insulating materials.
NN
NN
oo
oo
tt
tt
ee
ee
When installing the drain pump, leave a 7mm space
between the bottom of the drain pan and the drain pump.
NN
NN
oo
oo
tt
tt
ee
ee
Connect the drain pump cable to yellow terminal(CN74)
and the float switch to black terminal(CN51).
NN
NN
oo
oo
tt
tt
ee
ee
Switch No.
K4
Switch Position
ON
OFF
Using Drain Pump
X
O
K1 K2 K3 K4
SW03
Drain pump
Drain pump
7mm
Bottom of the drain pan
Accessories
Cable-tie
2
Drain pump &
Float switch
1
M4x12
Tapped screw
4
Cable clamp
2
Float switch