Installation manual

Connecting the Refrigerant Pipe
There are two refrigerant pipes of differing diameters:
A smaller one for the liquid refrigerant
A larger one for the gas refrigerant
The inside of copper tube must be clean & has no dust.
The connection procedure for the refrigerant pipes varies according to
the exit position of the pipes from the indoor unit, as seen when facing
the indoor in the “A” side.
Liquid refrigerant port
Gas refrigerant port
Drain hose port
Remove the pinch pipe on the pipes and connect the assembly pipes to
each pipe, tightening the nuts, first manually and then with a wrench, a
spanner applying the following torque.
1
Must use insulator which is thick enough to cover the refrigerant tube to
protect the condensate water on the outside of pipe falling onto the floor
and the efficiency of the unit will be better.
2
Cut off any excess foam insulation.
3
Be sure that there must be no crack or wave on the bended area.
4
It would be necessary to double the insulation thickness(10mm or more)
to prevent condensation even on the insulator when if the installed area is
warm and humid.
5
If the pipes must be shortened refer to page 10.
NN
NN
oo
oo
tt
tt
ee
ee
Outer Diameter Torque (kgf•cm)
6.35 mm (1/4") 144~176
9.52 mm (3/8") 333~407
12.70 mm (1/2") 504~616
15.88 mm (5/8") 630~770
19.05 mm (3/4") 990~1210
22.23 mm (7/8") 990~1210
Liquid refrigerant port
Drain hose port
Gas
refrigerant
port
A
E-9
ENGLISH