Page 11 of 13 Report No.: 236145
IEC60335_2_40F ATTACHMENT 1
EN 60335-1, EN 60335-2-40
Clause Requirement – Test Result Remark Verdict
National Differences / Deviations for United Kingdom
ZA ANNEX ZA (NORMATIVE), SPECIAL NATIONAL CONDITIONS (EN 60335-1,
EN 60335-2-40)
25.6 Plugs according to standard sheet C2b not allowed No plugs.
The manufacturer, service
agent or similarly qualified
person shall use a proper
cross sectional area of supply
cord and interconnection cord
referring to an installation
manual.
N/A
Plugs according to standard sheet C3b not allowed N/A
Only plugs according to standard sheets B2 and C5
allowed (see also annex ZB)
N/A
25.8 Replacement of line for 10 A and 16 A by:
> 10 A and 13 A 1,25 mm²
N/A
> 13 A and 16 A 1,5 mm²
No plugs.
The manufacturer, service
agent or similarly qualified
person shall use a proper
cross sectional area of supply
cord and interconnection cord
referring to an installation
manual.
N/A
ZB ANNEX ZB (INFORMATIVE), A-DEVIATIONS (EN 60335-1, EN 60335-2-40)
25.6 These regulations apply to all plugs for domestic use
at a voltage of not less than 200 V and allow only
plugs to BS 1363 to be fitted to domestic appliances.
It also allows plugs to BS 4573 and standard
sheet C5 to be fitted to shavers and toothbrushes.
No plugs. N/A
ZAA ANNEX ZAA (INFORMATIVE) (EN 60335-2-40/A11)
THE RELEVENCE OF THE PRESSURE EQUIPMENT DIRECTIVE
Refrigerating systems having a pressure greater
than 0,05 MPa are considered to be assemblies
falling within the scope of the Pressure Equipment
Directive, 97/23/EC. However, according to
Article 1, item 3.6 of the directive, equipment
classified no higher than category I and covered by
the low voltage directive is excluded from its scope.
(EN 60335-2-40/A11)
N/A