RCMHXGA RCMHXEA Air to Water Heat Pump Mono Outdoor Unit installation manual imagine the possibilities Thank you for purchasing this Samsung product. To receive more complete service, please register your product at www.samsung.
Contents Safety Precautions....................................................................................................................................................................................................................2 Product Specifications . .........................................................................................................................................................................................................4 Application Examples ......................
Do not attempt to repair, move, alter or reinstall the unit by unauthorized personnel, these operations may cause product damage, electric shocks and fires. Do not place containers with liquids or other objects on the unit. All the materials used for the manufacture and packaging of the air to water heat pump are recyclable. The packing material and exhaust batteries of the remote controller(optional) must be disposed of in accordance with local regulations.
Product Specifications Product Line-up Line-up Remark Chassis Heat Pump Units - Model Name RC120MHXEA RC120MHXGA RC140MHXEA RC140MHXGA RC160MHXEA RC160MHXGA RC090MHXEA MIM-E03A Auxiliary Parts Requisite Control Kit Standard models: NH200CHXEA NH300CHXEA Option Domestic Hot Water tank Solar connected NH200CHXES NH300CHXES Accessories Keep supplied accessories until the installation is finished. Hand the installation manual over to the customer after finishing installation.
Product Specifications Unit RC120MHXEA RC120MHXGA RC140MHXEA RC140MHXGA RC160MHXEA RC160MHXGA Power Source - 1P, 220~240VAC 50Hz 3P, 380-415VAC 50Hz 1P, 220~240VAC 50Hz 3P, 380-415VAC 50Hz 1P, 220~240VAC 50Hz 3P, 380-415VAC 50Hz 7°C kW 12.0 14.0 16.0 2°C kW 10.0 13.0 15.0 -15°C kW 12.5 12.5 12.5 COP (A7-W35) - 4.70 4.50 4.
Product Specifications Type Unit RC090MHXEA Power Source - 1P, 220~240VAC 50Hz 7°C kW 9 2°C kW 9 -15°C kW 7 COP (A7-W35) - 4.1 Compressor - Rotary Inverter Condenser - Brazing type 48 plates Evaporator - Φ7, FP 1.6, L850 Fan & Motor - Propeller, Φ520, 3-blade BLDC Inverter Flow Switch LPM 16 ± 1.5 Magnetic (decreasing) Base Heater W 150 Refrigerant g 1,850 (R410A) Noise (Heat/Cool, Pressure) dB 63/ 60 Water Connection (In/Out) Inch 1.0 / 1.
Application Examples ENGLISH • The application examples given below are for illustration purposes only. • When the SAMSUNG Air-to-Water Heat Pump system is used in series with another heat source (e.g. gas boiler), ensure that the return water temperature not exceed 55°C. • The unit is only to be used in a closed water system. Application in an open water circuit can lead to excessive corrosion of the water piping.
Application Examples Application #2 Mono Outdoor + Cylinder Unit RF Receiver Expansion Vessel Supply Header Wired Controller Return Header From City Water Control Kit (provided by SAMSUNG) Radiators or Convectors Hot water Supply P Room Thermostat (Wireless) T B T F T Supply Header Return Header Under-Floor Heating Coils Indoor Outdoor Outdoor unit 8 Cylinder Unit
Main Components Dimensions(Overall) ENGLISH Heat Pump for R410A.
Main Components Dimensions (Water pipe) RC120MHX/RC140MHX/RC160MHX RC090MHX 513.4 151.5 244.4 83.
Components(RC090) ENGLISH ③ ① ② NO. 1 2 3 Name PHE Base Heater Water fitting Note.
Main Components Components(RC120/140/160) ① ④ ⑤ ③ ② NO. 1 2 3 4 5 12 Name PHE Base Heater Water Hose In Water Hose Out Water fitting Note.
Functional Diagram (RC090MHX) ENGLISH 4WAY v/v T/S #7 T/S #1 T/S #3 S/V S/V PHE T/S #5 T/S #2 T/S #4 Comp Filter Exp.
Functional Diagram (RC120MHX/RC140MHX/RC160MHX) 4WAY v/v T/S #7 HP s/w T/S #1 T/S #3 S/V S/V PHE T/S #5 T/S #2 T/S #4 Comp Filter 14 Exp.
Installing the Unit Moving the Outdoor Unit Select the moving route in advance. Be sure that moving route is safe from weight of the outdoor unit. Do not slant the product more than 30˚when carrying it. (do not lay the product down sideways) The surface of the heat exchanger is sharp. Be carefule not to be injured while moving and installing. ENGLISH • • • • Moving the Outdoor Unit by Wire Rope Fasten the outdoor unit by two 8m or longer wire ropes as shown at the figure.
Installing the Unit - Install the outdoor unit in a place (such as near buildings etc.) where it can be prevented from sea breeze which can damage the outdoor unit. Outdoor Sea unit breeze Sea breeze Sea Outdoor unit Sea - If you cannot avoid installing the outdoor unit by the seashore, construct a protection wall around to block the sea breeze.
Space Requirements for Outdoor Unit When installing 1 outdoor unit 1500 or more 300 or more When the air outlet is towards the wall 2000 or more 600 or more W hen 3 sides of the outdoor unit are blocked by the wall 300 or more T he upper part of the outdoor unit and the air outlet is opposite the wall T he upper part of the outdoor unit and the air outlet is towards the wall 1500 or more 300 or more 300 or more 600 or more 1500 or more 300 or more ENGLISH When the air outlet i
AA Installing the Unit When installing more than 1 outdoor unit 1500 or more (Unit : mm) 300 or more When the air outlet is towards the wall 600 or more 600 or more 300 or more 600 or more 1500 or more 600 or more When front and rear side of the outdoor unit is towards the wall 1500 or more 600 or more 3000 or more 3000 or more 500 or more 600 or more When 3 sides of the outdoor unit are blocked by the wall 500 or more 300 or more 300 or more 300 or more T he upper part of
Outdoor unit installation Fix the outdoor unit with anchor bolts. (Unit : mm) Anchor bolt hole 328 • When tightening the anchor bolt Tighten the rubber washer to prevent the outdoor unit bolt connection part from corroding • Make a drain outlet around the base for outdoor unit drainage. • If the outdoor unit is installed on the roof, you have to check the ceiling strength and waterproof the unit. 384 330 • The anchor bolt must be 20mm or higher from the base surface.
Installing the Unit Drain work While Air-Water Heat Pump is running in heating mode, Ice can begin accumulate on the surface of condenser. To prevent Ice growing, system go into De-frost mode and then Ice on the surface changes to water. Dropped water from condenser shall be eliminated through running drain holes to prevent Ice growing at low temperature. ≥100mm In case there is not enough space for drainage out of the unit, additional drain works are required.
Selecting a location in cold climates ENGLISH • When operating the unit in a low outdoor ambient temperature, be sure to follow the instructions described below. To prevent exposure to wind, install the unit with its suction side facing the wall. Never install the unit at a site where the suction side may be exposed directly to wind. To prevent exposure to wind, install a baffle plate on the air discharge side of the unit.
Piping Work Water connections must be made in accordance with the outlook diagram delivered with the unit, respecting the water in- and outlet. If air, moisture or dust gets in the water circuit, problems may occur. Therefore, always take into account the following when connecting the water circuit: Use clean pipes only. Hold the pipe end downwards when removing burrs. Cover the pipe end when inserting it through a wall so that no dust and dirt enter.
Flushing and air-purging 6. Circulate for long enough to ensure that all air has been bled from the complete water piping system. • After installations, commissioning should be performed by qualified representatives. Unless flushing and air-purging works are performed adequately, it might result in malfunctions. Flushing unit (or purging cart) 23 ENGLISH When filling water, the following start-up procedure should be followed. 1. All system components and pipes must be tested for the presence of leaks.
Piping Work Before installing/commissioning the unit, make sure to check the following points; - The maximum water pressure of the unit is 2.8 bar static pressure. - The operating range of water temperature is 15~55˚C at heating conditions and 5~25˚C at cooling conditions. - The minimum required water flow for operation is 12~16 liters/min. At all times the required water flow-rates should remain. Otherwise, the unit can stop due to a lack of water.
Setting capacity and pre-pressure of the expansion vessel ENGLISH When it is required to change the default pre-pressure of the expansion vessel(1 bar), keep in mind the following guidelines: Use only dry nitrogen to set the expansion vessel pre-pressure. Inappropriate setting of the expansion vessel pre-pressure will lead to malfunction of the system. Therefore, the pre-pressure should only be adjusted by a licensed installer. Pre-pressure(bar) 2.5 2.0 1.5 Operation range 1.0 0.5 0.
Piping Work Unit Resistance and PHE resistance by Glycol concentrate The unit is composed of water pipes and PHE basically. To ensure correct operation and predict the expected performance, Flow and Resistance table can be used. And Flow and Resistance characteristic is dependent on on Glyco concentrate.
Charging Water ENGLISH After installation is completed, the following procedures shall be used to charge water into the hydro unit. Connect water lines to water connections of Air-Water Heat Pump. Air vent valve shall be open at least 2turns so that air can be eliminated in the system. Open the service valve in the water supply connection. Water pressure of supply line shall be over 2.0 bar for good charging work. Stop water supply when the pressure gauge of hydro unit indicates around 2.
Piping Work Pressure relief valve MONO Unit does not have a pressure relief valve. The valve shall prevents abnomal water pressure from damaging the the system by opening at 3.0 bar . • Make certain that the discharged water out of drain pan does not affect other elements. Filter / Strainer Installation of Filter / Strainer is mandatory for water system. The Filter or Strainer shall be located in front of inlet pipe of PHE.
AA Wiring • During the unit installation make first refrigerant connections and then electrical connections. If unit is uninstalled first disconnect electrical cables, then refrigerant connections. • Connect the air conditioner to grounding system before performing the electrical connection. • When installing the unit, you shouldn't use inter connection wire.
AA Wiring Power Cable Specifications Single Phase Type of outdoor unit Outdoor Power supply A RC090MHXEA 1Φ, 220-240V, 50Hz B RC120MHXEA 1Φ, 220-240V, 50Hz C RC140MHXEA RC160MHXEA 1Φ, 220-240V, 50Hz Power cable MAX. LENGTH mm²,wires m 4.0/3 <10m 6.0/3 10m
Between Indoor unit and Outdoor unit Connection Cable Specifications(Common in use) Home Server 0.75mm², 2wires 0.75mm², 2wires ENGLISH Communication Cable For Indoor Power Cable, use the grade H07RN-F or H05RN-F materials. When installing the indoor unit in a computer room or network room, use the double shielded (Tape aluminum / polyester braid + copper ) cable of FROHH2R type. 1-phase terminal block spec AC power : M5 screw L Communication : M3 screw N 6.7 12 9.
AA Wiring Wiring Diagram of Power Cable When using ELB for 1 phase and 3 phase 1 phase L N Cable tie Power Supply Electrical component box Cable clamp MCCB ELB Main power cable MCCB Communication cable 3 phase L1(R) L2(S) L3(T) N Indoor Unit Cable tie The appearance of the unit may be different from the picture depending on the model.
Wiring Diagram of Connection Cord 1 phase 3 phase L N F2 F1 L Control kit F2 F1 L1(R) L2(S) L3(T) N ENGLISH Control kit L N N F1 F2 Cable tie Cable tie Cable clamp Communication cable 3 Phase 4 Wires power cable (AC 380V) Main power cable Communication cable Cable clamp • Lay the electrical wiring so that the front cover does not rise up when doing wiring work and attach the front cover securely.
AA Wiring C onnect the rated cables only. Connect using a driver which is able to apply the rated torque to the screws. If the terminal is loose, fire may occur caused by arc. If the terminal is connected too firmly, the terminal may be damaged. M3 M4 M5 5.0~6.0 12.0~15.0 20.0~25.
Testing operations AA 1. Check the power supply between the outdoor unit and the auxiliary circuit breaker. 1 phase power supply : L, N 2. Check the indoor unit. 1) C heck that you have connected the power and communication cables correctly. (If the power cable and communication cables one mixed up or connected incorrectly, the PCB will be damaged.) 2) C heck the thermistor sensor, drain pump/hose, and display are connected correctly. 3.
Testing AA operations 6. View Mode : When the K4 switch is pressed, you can see information about our system state as below.
Trouble shooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center. ENGLISH Outdoor unit If an error occurs during the operation, it is displayed on the outdoor unit PCB LED, both MAIN PCB and INVERTER PCB. No.
Maintenance Listed checks and inspections shall be implemented regularly so that the unit can operate as design intention in production site. Always switch off the unit and remove power cable from the electric source before carrying out any maintenance or repair works. Mentioned actions shall be carried out at least once a year by qualified personnel. 1. Water pressure - Check if the water pressure is above 0.3 bar. If necessary, supplement water. 2.
Adding refrigerant Procedures as below is describing how to adding the amount of refrigerant. • R410A Shall be added as liquid phase. • Adding and recharging works shall be by Service valves. 1. Connect the manifold gauge and purge the manifold gauge. 2. Open the manifold gauge valve of the liquid side service valve and add the liquid refrigerant. 3.
Maintenance Important information regulation regarding the refrigerant used This product contains fluorinated greenhouse gases covered by the Kyoto Protocol. Do not vent gases into the atmosphere. • Inform user if system contains 3 kg or more of fluorinated greenhouse gases. In this case, it has to be checked for leakage at least once every 12 months, according to regulation n°842/2006. This activity has to be covered by qualified personnel only.
Memo 41
Memo 42
Memo AA 43