20 Replacement of Parts
Diagram 20.13
9744
BOILER DRAIN
VALVE
Diagram 20.14
WATER FLOW
SENSOR
11590
F30E/F35E Only
9758
Diagram 20.15
SYSTEM WATER PRESSURE
SENSOR
F30E shown
BYPASS VALVE
20.23 Boiler drain point, refer to diagram 20.13.
Before starting refer to the front of Section 20 Important
information.
• Remove the front panel, refer to Section 17.3.
• Lower the control panel, refer to Section 17.4.
• Drain down the boiler only, refer to relevant part of diagram
20.1.
Pull out slotted metal clip securing boiler drain valve into
housing, remove boiler drain valve.
20.24 (F30E/F35E Only) Water flow sensor, refer to
diagram 20.14.
Before starting refer to the front of Section 20 Important
information.
• Remove the front panel, refer to Section 17.3.
• Lower the control panel, refer to Section 17.4.
Drain down the boiler, refer to relevant part of Section 20.1.
• Undo the union nut on the cold water inlet isolating valve.
• Pull out slotted metal clip securing filling system tap into
housing, swing the tap forwards.
• Pull out the two slotted metal clips retaining the domestic
water inlet filter housing.
• Remove domestic water inlet filter housing.
• Remove electrical connections from water flow sensor.
• Pull off slotted metal clip and remove water flow sensor.
20.25 System water pressure sensor, refer to diagram
20.15.
Before starting refer to the front of Section 20 Important
information.
• Remove the front panel, refer to Section 17.3.
• Lower the control panel, refer to Section 17.4.
Drain down the boiler, refer to relevant part of Section 20.1.
• Remove electrical connections from water pressure sensor.
• Pull off slotted metal clip and remove water pressure sensor.