Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
Ubr [Braking level]
335 to 820 V According to drive rating
voltage
T
Braking transistor command level.
LbA [Load sharing]
[No] (nO)
g
When 2 motors are connected mechanically and therefore at the same speed, and each is controlled by a drive, this function
can be used to improve torque distribution between the two motors. To do this, it varies the speed based on the torque.
This parameter can only be accessed if [Motor control type] (Ctt) page 92
is set to [SVC V] (UUC).
nO
YES
[No] (nO): Function inactive
[Yes] (YES): Function active
LbC [Load correction]
0 to 599 Hz 0 Hz
g
T
Rated correction in Hz.
This parameter can be accessed if [Load sharing] (LbA) is set to [Yes] (YES).
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
LbC
LbC
Torque
Nominal torque
Nominal torque
Frequency
0
DRI- > CONF > FULL > DRC-