Configuration Mode (ConF)
S1A28692 03/2010 111
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
LbC1 [Correction min spd]
0 to 598.9 Hz 0 Hz
g
T
This parameter can be accessed if [Load sharing] (LbA) is set to [Yes] (YES).
Minimum speed for load correction in Hz. Below this threshold, no corrections are made. Used to cancel correction at very low
speed if this would hamper rotation of the motor.
LbC2 [Correction max spd]
[Correction min spd]
(LbC1) + 0.1 at 599 Hz
0.1 Hz
g
T
This parameter can be accessed if [Load sharing] (LbA) is set to [Yes] (YES).
Speed threshold in Hz above which maximum load correction is applied.
LbC3 [Torque offset]
0 to 300% 0%
g
T
This parameter can be accessed if [Load sharing] (LbA) is set to [Yes] (YES).
Minimum torque for load correction as a % of the rated torque. Below this threshold, no corrections are made. Used to avoid
torque instabilities when the torque direction is not constant.
LbF [Sharing filter]
0 to 20 s 100 ms
g
T
This parameter can be accessed if [Load sharing] (LbA) is set to [Yes] (YES).
Time constant (filter) for correction in ms. Used in the event of flexible mechanical coupling in order to avoid instabilities.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
T
Parameter that can be modified during operation or when stopped.
DRI- > CONF > FULL > DRC-