Installation manual

Configuration Mode (ConF)
114 S1A28692 03/2010
Parameters described in this page can be accessed by:
L1- [LI1 CONFIGURATION]
L1A [LI1 assignment]
nO
rUn
Frd
rrS
rPS
JOG
USP
dSP
PS2
PS4
PS8
rFC
nSt
dCI
FSt
FLO
rSF
tUL
SPM
FLI
PAU
PIS
Pr2
Pr4
tLA
EtF
rCA
CnF1
CnF2
CHA1
CHA2
tLC
CCS
InH
PS16
LC2
LAF
LAr
rCb
trC
bCI
SAF
SAr
dAF
dAr
CLS
LES
rtr
SnC
rPA
SH2
SH4
LO1
r1
r2
dO1
btUC
OIr
FJOG
FPS1
FPS2
Read-only parameter, cannot be configured.
It displays all the functions that are assigned to input LI1 in order to check for multiple assignments.
[No] (nO): Not assigned
[Run] (rUn): Run Enable
[Forward] (Frd): Forward operation
[Reverse] (rrS): Reverse operation
[Ramp switching] (rPS): Ramp switching
[Jog] (JOG): Jog operation
[+Speed] (USP): + speed
[- speed] (dSP): - speed
[2 preset speeds] (PS2): 2 Pr
eset speeds
[4 preset speeds] (PS4): 4 Preset speeds
[8 preset speeds] (PS8): 8 Preset speeds
[Ref. 2 switching] (rFC): Reference switching
[Freewheel stop] (nS t): Freewheel stop
[DC injection] (dCI): Injection DC stop
[Fast stop] (FSt): Fast stop
[Forced local] (FLO): Forced local mode
[Fault reset] (rSF): Fault reset
[Auto-tuning] (tUL): Auto-tuning
[Ref. memo.] (SPM): Save reference
[Pre Fluxing] (FLI): Motor fluxing
[Auto / manual] (PAU): PI(D) auto-manu
[PID integral reset] (PIS): Integral shunting PI(D)
[2 preset PID ref.] (Pr2): 2 Preset PI(D)
references
[4 preset PID ref.] (Pr4): 4 Preset PI(D) references
[Torque limitation] (tLA): Permanent torque limitation
[External fault] (EtF): External fault
[Output contact. fdbk] (rCA): Downstream contactor feedback
[2 config. switching] (CnF1): Configuration switching 1
[3 config. switching] (CnF2): Configuration switching 2
[2 parameter sets] (CHA1): Parameter switching 1
[3 parameter sets] (CHA2): Parameter switching 2
[Activ. Analog torque limitation] (tLC): Torque limitation: Activation (analog input) by a logic input
[Cmd switching] (CCS): Command channel switching
[Fault inhibition] (InH): Fault inhibition
[16 preset speeds] (PS16): 16 preset speeds
[Current limit 2] (LC2): Current limitation switching
[Stop FW limit sw.] (LAF): Limit
attained forward
[Stop RV limit sw.] (LAr): Limit attained reverse
[Ref 1B switching] (rCb): Reference channel switching (1 to 1B)
[Traverse control] (trC): Traverse control
[Brake contact] (bCI): Brake logic input contact
[Stop FW limit sw.] (SAF): Stop switch forward
[Stop RV limit sw.] (SAr): Stop switch reverse
[Slowdown forward] (dAF): Slowdown attained forward
[Slowdown reverse] (dAr): Slowdown attained reverse
[Disable limit sw.] (CLS): Limits switches clearing
[Drive lock (Line contact. ctrl)] (LES): Emergency stop
[Init. traverse ctrl.] (rtr): Reload traverse control
[Counter wobble] (SnC): Counter wobble synchronization
[Prod. reset] (rPA): Reset Product
[2 HSP] (SH2): High Speed 2
[4 HSP]
(SH4): High Speed 4
[L
O1] (LO1): Logical output LO1
[R1] (r1): Relay R1
[R2] (r2): Relay R2
[DO1] (dO1): Analog/logical output DO1
[Bth visibilit.] (btUC): Bluetooth visibility
[Regen. connection] (OIr): Operation with reversible unit
[Jog] (FJOG): Function key jog assignment
[Preset spd2] (FPS1): Function key preset speed 1 assignment
[Preset spd3] (FPS2): Function key preset speed 2 assignment
Code Name / Description Adjustment range Factory setting
DRI- > CONF > FULL > I_O- > L1-
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com