Installation manual

Configuration Mode (ConF)
S1A28692 03/2010 115
Parameters described in this page can be accessed by:
FPr1
FPr2
FUSP
FdSP
Ft
USI
dSI
IL01
...
IL10
FbrM
[PID ref. 2] (FPr1): Function key preset PI 1 assignment
[PID ref. 3] (FPr2): Function key preset PI 2 assignment
[+Speed] (FUSP): Function key faster assignment
[-Speed] (FdSP): Function key slower assignment
[T/K] (Ft ): Function key bumpless assignment
[+speed around ref.] (USI): + Speed around ref
[-speed around ref.] (dSI): - Speed around ref
[IL01] (IL01): Function blocks: Logical Input 1
...
[IL10] (IL10): Function blocks: Logical Input 10
[FB start] (FbrM): Function blocks: Run mode
L1d [LI1 On Delay]
0 to 200 ms 0 ms
This parameter is used to take account of the change of the logic input to state 1 with a delay that can be adjusted between 0
and 200 milliseconds, in order to filter out possible interference. The change to state 0 is taken into account without delay.
I_O- [INPUTS / OUTPUTS CFG] (continued)
L2-
to
L6-
[LIx CONFIGURATION]
All the logic inputs available on the drive are processed as in the example for LI1 above, up to LI6.
L5-
[LA5 CONFIGURATION]
Specific parameters for LI5 used as a pulse input.
PIA [RP assignment]
Read-only parameter, cannot be configured.
It displays all the functions associated with the Pulse input in order to check, for example, for compatibility problems.
Identical to [AI1 assignment] (A11A) page 120
.
PIL [RP min value]
0 to 20.00 kHz 0 kHz
Pulse input scaling parameter of 0% in Hz * 10 unit.
PFr [RP max value]
0 to 20.00 kHz 20.00 kHz
Pulse input scaling parameter of 100% in Hz * 10 unit.
PFI [RP filter]
0 to 1,000 ms 0 ms
I/O ext Pulse input cutoff time of the low-filter.
LA1-
LA2-
[LAx CONFIGURATION]
The 2 analog inputs AI1 and AI2 on the drive could be used as LI inputs and are processed as in the example for LI1 above.
g
These parameters only appear if the corresponding function has been selected in another menu. When the parameters can
also be accessed and adjusted from within the configuration menu for the corresponding function, their description is detailed
in these menus, on the pages indicated, to aid programming.
To change the assignment of this parameter, press the ENT key for 2 s.
Code Name / Description Adjustment range Factory setting
2 s
DRI- > CONF > FULL > I_O- > L1-