Installation manual

Configuration Mode (ConF)
118 S1A28692 03/2010
Parameters described in this page can be accessed by:
Code Name / Description Adjustment range Factory setting
I_O- [INPUTS / OUTPUTS CFG] (continued)
LA1- [LAI CONFIGURATION]
bSP [Reference template]
[Standard] (bSd)
bSd
T
bLS
bnS
bnS0
[Standard] (bSd)
[Pedestal] (bLS)
[Deadband] (bnS)
[Deadband 0] (bnS0)
T
Parameter that can be modified during operation or when stopped.
Frequency
Reference
LSP
-100%
+100%
HSP
LSP
HSP
0%
At zero reference the frequency = LSP
Frequency
Reference
LSP
-100%
+100%
HSP
LSP
HSP
At reference = 0 to LSP the frequency = LSP
Frequency
Reference
LSP
-100%
+100%
HSP
LSP
HSP
0
At reference = 0 to LSP the frequency = 0
Frequency
Reference
LSP
-100%
+100%
HSP
LSP
HSP
0%
This operation is the same as [Standard] (bSd), except that in
the following cases at zero reference, the frequency = 0:
The signal is less than [Min value], which is greater than 0 (example
1 V on a 2 - 10 V input)
The signal is greater than [Min value], which is greater than
[Max value] (example: 11 V on a 10 - 0 V input).
If the input range is configured as "bidirectional", operation remains
identical to [Standard] (bSd).
This parameter defines how the speed reference is taken into
account, for analog inputs and Pulse input only. In the case of the
PID regulator, this is the PID output reference.
The limits are set by the [Low speed] (LSP) and
[High speed] (HSP) parameters, page 75
.
DRI- > CONF > FULL > I_O- > LAI-